Number of Natural Roof Ventilator by Area Calculations
For Model : A-14S, A-18S, A-22S, A-22, S22, A-25S, A-25, S25, A-30 and A-39
 
1. Area Calculation
 
Formula :
(Put Building Dimension)
Width x Length x Height
  90 x 120 x 5
Building Volume = 54,000.00 M3 (CU.M)
 
2. Airchange Calculation

Choose airchange / hr. classified by the utilization.

 
Utilization (Installation Area) AIRCHANGE/HR.
   Warehouse 5-7.5
   Worker Area / Factory 10-15
   Machine Area / Manufacture 15-25
   Kitchen (High temperature Room) 25 or more
   Spraypaint Chamber / Pollution Room 30-100
 
Formula Building Volume x AIRCHANGE
/HR.
÷ 60 minute
  54,000.00 x 25 ÷ 60
Total Airchange Volume = 22,500.00 CMM.
 
 
 
3. Number of Power Roof Ventilator Calculation
Capacity of Power Roof Ventilators in each model :
 
A-14S = 33 CMM.
A-18S = 43 CMM.
A-22S, A-22, S22 = 80 CMM.
A-25S, A-25, S25 = 90 CMM.
A-30 = 111 CMM.
A-39 = 162 CMM.
 
Formula : ( Choose the model for installation ) Example MODEL : A-25S
 
Total Airchange Volume ÷ Capacity of each model. = Total Number for Installation
22,500.00 ÷ 90.00 = 250.00 Sets
 
** Calculation can be varied in utilization which also depend on condition of each building **
Remark : Example is for installation of ventilator in manufacture or machine area.
 
+ BACK
 
Home | Products | News & Activities | Careers | Reference Projects | FAQ | Engineering Tips  
Artith Ventilators Ltd., Part.
Head office : 55 Moo 9, Ramindra Rd.,
Kannayao, Kannayao, Bangkok 10230 Thailand
Tel. (66)-2510-1339, 2509-3065, 2509-2884
Fax : (66)-2943-1814
E-mail :
contact@artith.com
© Copyright 2007 Artith Ventilators Ltd., Part. All right reserved. Design by 1001 Click